Skip to content

Tag: Fronius

Issue Solved: Fronius MPPT1 dropping production

I’ve been fighting with two identically installed Fronius Symo Advanced (10kW) inverters over the last month, and I think I’ve finally fixed it. It’s very strange, and seems to be an issue in the firmware of the inverter, itself.

The installation looks like this. They are two carports (only one is pictured), identically oriented, with north, south, east, and west arrays. The east and west arrays are smaller and hooked up to a Fronius Primo 3.8 on each carport, obviously using different MPPTs for different arrays. The same thing is the case for the north and south arrays: they’re hooked up to a Symo Advanced 10.0 at each carport.

The problem is that MPPT1, hooked up to the north array on each carport, drops off during high irradiance days. Check it out.

You can see when it starts producing in the morning, drops to nothing, then later in the day, it jumps back up and starts producing. Sometimes it takes until after noon, and sometimes, like pictured above, it comes back up when the irradiance dips and MPPT2 produces less for a bit.

This only happens on higher irradiance days with good, bright sun, and on both carports. On cloudier days, both north and south arrays on both carports produce equally, as you’d expect with diffuse sun.

Fronius tech support was no help with this one. We made sure firmware was up to date (fro34310 at the time, for those following along), but beyond that they were extremely confident that there was something wrong with our wiring or our array setup, but couldn’t give me proper direction. It may have simply been the one tech I was talking to, but he was extremely frustratingly not budging on his assessment. It doesn’t help that there are no error codes triggered with this problem.

In troubleshooting, I couldn’t nail any issues to our set up for rapid shutdown devices; everything on site is rated to work with each other and is set up properly. Had some previous issues with dueling RSD transmitters tripping arc faults that I got sorted, so very confident that’s not an issue any more.

When I was onsite, however, I was able to shut off DC to the inverter and turn it back on within about 10-20 seconds, and the inverter jumped up to the proper production on all strings, so it would seem there’s nothing instantaneous in the array that’s causing MPPT strangeness.

Finally, I swapped MPPTs between arrays, putting the south array (highest producing) on MPPT1 and the north array (lowest producing) on MPPT2. After giving it some time, I think this one change solved my issue.

You can see in comparison to the first graph, that the north arrays seem to have no more issues with dropping off in production. The south arrays didn’t have the irradiance on this day that they had in the previous graph, but it’s enough that the north arrays would have dropped off if they were wired as they were originally.

My reckon is that this is directly related to the inverter wigging out when MPPT2 gets 5x or more the production of MPPT1, and only resets when MPPT2 stops rising. I’d imagine that most installations would put the main and highest producing arrays on MPPT1 by default anyway, so this issue would be very rarely seen. If you’re having this issue, try making sure MPPT1 gets the most production between the two, and it might fix it for you.

Weird weird issue.

Fronius STATE 301

Inverter at question is a Fronius IG Plus 10kW, installed in 2010. When I arrived, the AC was turned off. Turned AC back on, plugged Data Logger back in. The first time the inverter finished its startup cycle, the house lights kinda blinked a little bit and it threw a 301 error code (Overcurrent sensor, but typically an inverter problem) . Second time it finished the startup cycle, it successfully started producing at about 3500 watts. Given that it’s 10:30 AM and clear outside, I’d expect it to be producing much higher than that. After the Data Logger booted, it started beeping regularly, flashing all 4 signal lights as red.

Tech support confirmed my suspicions. We checked the other power stages’ states and both were 306 (Insufficient PV Power, which is not the problem here). The inverter keeps clicking like it’s trying to activate the upper power stages, but is unsuccessful. He also said the Data Logger was likely dead.

Two solutions: We can pay to send the inverter back to be rebuilt, which only holds a 1 year warranty for the repaired parts, or buy a new inverter. Tech support said once all is said and done, we’d already be in for the cost of at least half a new inverter anyway. Most sensible solution is to buy the new inverter. As far as the Data Logger, most new inverters these days come with monitoring, so no worries there.